  • <tr id='uJhSQv'><strong id='uJhSQv'></strong><small id='uJhSQv'></small><button id='uJhSQv'></button><li id='uJhSQv'><noscript id='uJhSQv'><big id='uJhSQv'></big><dt id='uJhSQv'></dt></noscript></li></tr><ol id='uJhSQv'><option id='uJhSQv'><table id='uJhSQv'><blockquote id='uJhSQv'><tbody id='uJhSQv'></tbody></blockquote></table></option></ol><u id='uJhSQv'></u><kbd id='uJhSQv'><kbd id='uJhSQv'></kbd></kbd>

    <code id='uJhSQv'><strong id='uJhSQv'></strong></code>

    <fieldset id='uJhSQv'></fieldset>
          <span id='uJhSQv'></span>

              <ins id='uJhSQv'></ins>
              <acronym id='uJhSQv'><em id='uJhSQv'></em><td id='uJhSQv'><div id='uJhSQv'></div></td></acronym><address id='uJhSQv'><big id='uJhSQv'><big id='uJhSQv'></big><legend id='uJhSQv'></legend></big></address>

              <i id='uJhSQv'><div id='uJhSQv'><ins id='uJhSQv'></ins></div></i>
              <i id='uJhSQv'></i>
            1. <dl id='uJhSQv'></dl>
              1. <blockquote id='uJhSQv'><q id='uJhSQv'><noscript id='uJhSQv'></noscript><dt id='uJhSQv'></dt></q></blockquote><noframes id='uJhSQv'><i id='uJhSQv'></i>

                English | 加入收藏 | 设为首页

                当前位置:首页->业务导航->经验反馈

                2019年7月5日宁德核电厂1号机组发生“因6.6kV应急配电系统B列应急母线失电导致手动停堆后撤”运行事件

                来源: 发布时间: 2019-07-10 14:33:00

                2019年7月5日04:05,宁德核电厂1号机组6.6kV应急配电系统B列应急母线发生失电,05:09工作人员按照规程执行手动停堆,并执行降温降压操作向余热排出系统冷却正常停堆模式后撤。经故障处理后,1号机组6.6kV应急配电系统B列母线于18:39恢复送电。

                7月5日22:19,主控触发1号机组6.6kV配电系统A列母线绝缘低报警,停运配电盘检查处理。7月6日23:18,A列母线回复送电。

                经过电厂初步分析,1号机组6.6kV应急配电系统B列应急母线发生失电的原因为重要厂用水系统4号泵电机A、C相相间短路,过电压引发6.6kV应急配电系统B列开关进线相间短路,导致B列6.6kV应急母线过流保护正常动作;6.6kV配电系统A列母线绝缘低报警的原因分析为重要厂用水系统3号泵电机进线侧绝缘子处爬电引起C相非金属性接地,引发6.6kV母线电压谐振。

                根据《核电厂营运单位报告制度》4.1.4“导致专设安全设施和反应堆保护系统自动或手动触发的事件”,本事件被界定为运行事件。

                本次事件过程中,机组无放射性后果、无人员照射、无环境污染。由于重要厂用水系统A/B列各有一台电机内部接地故障,考虑到“共因失效”附加因素,根据《国际核与辐射事件分级手册》,该事件界定为1级运行事件。